Technical Data - ABB REL 501-C1 2.5 Technical Reference Manual

Line distance protection terminal
Table of Contents

Advertisement

4.6
180
Supervision of AC input quantities (DA)
Parameter
Range
EventMask I
No Events,
Report Events
EventMask P
No Events,
Report Events
EventMask Q
No Events,
Report Events
EventMask f
No Events,
Report Events
EventMask S
No Events,
Report Events

Technical data

Table 175: Mean values (AC-monitoring)
Function
Frequency
Voltage (RMS) Ph-Ph
Current (RMS)
*)
Active power
*)
Reactive power
*) Measured at U
and 20% of I
r
Default
Unit
No Events
-
No Events
-
No Events
-
No Events
-
No Events
-
Nominal range
(0.95 - 1.05) x f
r
(0.1 - 1.5) x U
r
(0.2 - 4) x I
r
at |cos ϕ| ≥ 0.9
at |cos ϕ| ≤ 0.8
r
Description
Enables (Report Events) or disables (No
Events) the reporting of events from channel
DA12 to the SCS
Enables (Report Events) or disables (No
Events) the reporting of events from channel
DA13 to the SCS
Enables (Report Events) or disables (No
Events) the reporting of events from channel
DA14 to the SCS
Enables (Report Events) or disables (No
Events) the reporting of events from channel
DA15 to the SCS
Enables (Report Events) or disables (No
Events) the reporting of events from channel
DA16 to the SCS
Accuracy
± 0.2 Hz
± 2.5% of U
, at U ≤ U
r
± 2.5% of U, at U> U
± 2.5% of I
, at I ≤ I
r
r
± 2.5% of I, at I> I
r
± 5.0%
± 7.5%
Chapter 11
Monitoring
r
r

Advertisement

Table of Contents
loading