Input And Output Signals; Setting Parameters - ABB REL 501-C1 2.5 Technical Reference Manual

Line distance protection terminal
Table of Contents

Advertisement

3.4
3.5
160
Event function (EV)

Input and output signals

Table 160: Input signals for the EVENT (EVnn-) function block
Signal
INPUTy
NAMEy
T_SUPR01
T_SUPR03
T_SUPR05
T_SUPR07
T_SUPR09
T_SUPR11
T_SUPR13
T_SUPR15
PrColnn
INTERVAL
BOUND
FuncTEVnn
InfoNoy

Setting parameters

Table 161: Setting parameters for the EVENT (EVnn-) function
Parameter
Range
T_SUPR01
0.000-60.000
Step: 0.001
T_SUPR03
0.000-60.000
Step: 0.001
T_SUPR05
0.000-60.000
Step: 0.001
T_SUPR07
0.000-60.000
Step: 0.001
T_SUPR09
0.000-60.000
Step: 0.001
Description
Event input y, y=1-16
User name of signal connected to input y, y=01-16. String length up to
19 characters.
Suppression time for event inputs 1and 2
Suppression time for event inputs 3 and 4
Suppression time for event inputs 5 and 6
Suppression time for event inputs 7 and 8
Suppression time for event inputs 9 and 10
Suppression time for event inputs 11 and 12
Suppression time for event inputs 13 and 14
Suppression time for event inputs 15 and 16
Protocol for event block nn (nn=01-06). 0: Not used, 1: SPA, 2: LON,
3: SPA+LON, 4: IEC, 5: IEC+SPA, 6: IEC+LON, 7: IEC+LON+SPA.
Protocol for event block nn (nn=07-44). 0: Not used, 1: SPA, 2: LON,
3: SPA+LON
Time setting for cyclic sending of data
Input signals connected to other terminals on the network, 0: not con-
nected, 1: connected
Function type for event block nn (nn=01-06), used for IEC protocol
communication. Only present in blocks EV01-EV06.
Information number for event input y, y=01-16. Used for IEC protocol
communication. Only present in blocks EV01-EV06.
Default
Unit
Description
0.000
s
Suppression time for event input 1 and 3.
Can only be set using the CAP 540 configu-
ration tool.
0.000
s
Suppression time for event input 3 and 4.
Can only be set using the CAP 540 configu-
ration tool.
0.000
s
Suppression time for event input 5 and 6.
Can only be set using the CAP 540 configu-
ration tool.
0.000
s
Suppression time for event input 7 and 8.
Can only be set using the CAP 540 configu-
ration tool.
0.000
s
Suppression time for event input 9 and 10.
Can only be set using the CAP 540 configu-
ration tool.
Chapter 10
Logic

Advertisement

Table of Contents
loading