Serial communication
Table 196: Setting parameters for main function types
Parameter
Range
Operation
On, Off
MainFuncType
1-255
Path in local HMI: Configuration/TerminalCom/IECCom/Communication
Table 197: Setting parameters for IEC communication
Parameter
Range
SlaveNo
0-255
BaudRate
9600, 19200
Path in local HMI: Configuration/TerminalCom/IECCom/BlockOfInfoCmd
Table 198: IEC command
Command
Command description
BlockOfInfoCmd
Command with status and confirmation. Controls information sent to the master.

Technical data

Table 199: Serial communication (IEC 60870-5-103)
Function
Protocol
Communication speed
Table 200: Serial communication (RS485)
Function
Protocol
Communication speed

Serial communication, LON

Application

An optical network can be used within the Substation Automation system. This enables commu-
nication with the terminal through the LON bus from the operator's workplace, from the control
center and also from other terminals.
Default
Unit
Parameter description
Off
-
-
Main function types according to the stan-
dard
Default
Unit
Parameter description
30
-
Slave number
19200
Baud
Communication speed
Value
IEC 60870-5-103
9600, 19200 Bd
Value
SPA/IEC 60870-5-103
9600 Bd
Chapter 12
Data communication
193