Distance protection (ZM)
Table 81:
General setting parameters for ZM5 (ZMn--) function
Parameter
Range
Operation
Off, NoneDir,
Forward,
Reverse
Path in local HMI: Settings/Functions/Groupn/Impedance/Zone5
Table 82:
Settings for the phase-to-phase measurement ZM5 (ZMn--) function
Parameter
Range
Operation PP
Off, On
X1PP
0.10 - 400.00
Step: 0.01
R1PP
0.10 - 400.00
Step: 0.01
RFPP
0.10 - 400.00
Step: 0.01
Timer t5PP
Off, On
t5PP
0.000 -
60.000
Step: 0.001
Path in local HMI: Settings/Functions/Groupn/Impedance/Zone5
Table 83:
Settings for the phase-to-earth measurement ZM5 (ZMn--)
Parameter
Range
Operation PE
Off, On
X1PE
0.10 - 400.00
Step: 0.01
R1PE
0.10 - 400.00
Step: 0.01
Default
Unit
Description
Off
-
Operating mode and directionality for
ZM5
Default
Unit
Description
Off
-
Operating mode for ZM5 for Ph-Ph faults
10.00
ohm/ph
Positive sequence reactive reach of dis-
tance protection zone 5 for Ph-Ph faults
10.00
ohm/ph
Positive sequence line resistance
included in distance protection zone 5 for
Ph-Ph faults
10.00
ohm/loop
Resistive reach of distance protection
zone 5 for Ph-Ph faults
On
-
Operating mode of time delayed trip for
the distance protection zone 5 for Ph-Ph
faults
0.000
s
Time delayed trip operation of the dis-
tance protection zone 5 for Ph-Ph faults
Default
Unit
Description
Off
-
Operating mode for ZM5 for Ph-E faults
10.00
ohm/ph
Positive sequence reactive reach of dis-
tance protection zone 5 for Ph-E faults
10.00
ohm/ph
Positive sequence line resistance
included in distance protection zone 5 for
Ph-E faults
Chapter 4