General fault criteria (GFC)
Table 95:
General setting parameters
Parameter
Range
Operation
Off/On
INReleasePE
10-100
Step: 1
INBlockPP
10-100
Step: 1
Timer tPP
Off/On
tPP
0.000-60.000
Step: 0.001
Timer tPE
Off/On
tPE
0.000-60.000
Step:0.001
Path in local HMI: Settings/Functions/Groupn/Impedance/GenFltCriteria
Table 96:
Setting parameters for the overcurrent operating mode
Parameter
Range
Operation I>
Off/On
IP>
10-400
Step: 1
IN>
10-150
Step: 1
Setting parameters for the resistive and the reactive reach are given for terminals with rated cur-
rent Ir = 1A. All values should be divided by 5 for terminals with rated current Ir = 5A.
Path in local HMI: Settings/Functions/Groupn/Impedance/GenFltCriteria
Default
Unit
Description
Off
-
Operating mode
20
% of
3I0 limit for releasing phase-to-earth
lphMax
measuring loops
40
% of
3I0 limit for blocking phase-to-phase
lphMax
measuring loops
Off
-
Time delayed of trip for phase-to-phase
faults enabled or disabled
5.000
s
Time delay of trip for phase-to-phase
faults
Off
-
Time delay of trip for phase-to-earth faults
enabled or disabled
5.000
s
Time delay of trip for phase-to-earth faults
Default
Unit
Description
Off
-
Operation of current based GFC mea-
surement enabled or disabled
50
% of I1b
Set operate value for measured phase
currents
50
% of I4b
Set operate value for measured residual
current
Chapter 4
Line distance