ABB REL 501-C1 2.5 Technical Reference Manual page 179

Line distance protection terminal
Table of Contents

Advertisement

Disturbance report (DRP)
Table 166: Parameters for recording time
Parameter
Range
tPre
0.05-0.30
Step: 0.01
tPost
0.1-5.0
Step: 0.1
tLim
0.5-6.0
Step: 0.1
Path in local HMI: Settings/DisturbReport/BinarySignals/Inputn
Table 167: Parameters for reporting of binary signals
Parameter
Range
TrigOperation
Off, On
TrigLevel
Trig on 1, Trig
on 0
IndicationMask
Hide, Show
SetLed
Off, On
NAME
1 - 13
Default
Unit
Description
0.10
s
Prefault recording time
0.5
s
Postfault recording time
1.0
s
Fault recording time limit
Default
Unit
Description
Off
-
Determines if the signal should trigger
disturbance recording
Trig on 1
-
Selects the trigger signal transition.
Hide
-
Determines if the signal should be
included in the HMI indications list
Off
-
Determines if the signal should activate
the red HMI LED
Input n
Char
Signal name used in disturbance report
and indications. Can only be set from the
configuration tool.
( n =1-48)
Chapter 11
Monitoring
167