ABB REL 501-C1 2.5 Technical Reference Manual page 90

Line distance protection terminal
Table of Contents

Advertisement

78
General fault criteria (GFC)
Figure 31:
Operating characteristics of the GFC (impedance measuring principle) and zone
measuring elements
Figure
31
presents principally a shaped operate characteristic for an impedance based GFC func-
tion. Different designations have the following meaning:
XFW: reactive reach in forward direction
XRV: reactive reach in reverse direction
RF: resistive reach within the unlimited area
RLoad: resistive reach restricted by the minimum load impedance
LA: expected load impedance angle
jX
XFW
ZONE 3
ZONE 2
ZONE 1
LA
XRV
ZONE 4
Chapter 4
Line distance
R
RLoad
RF
99000189.vsd