78
General fault criteria (GFC)
Figure 31:
Operating characteristics of the GFC (impedance measuring principle) and zone
measuring elements
Figure
31
presents principally a shaped operate characteristic for an impedance based GFC func-
tion. Different designations have the following meaning:
•
XFW: reactive reach in forward direction
•
XRV: reactive reach in reverse direction
•
RF: resistive reach within the unlimited area
•
RLoad: resistive reach restricted by the minimum load impedance
•
LA: expected load impedance angle
jX
XFW
ZONE 3
ZONE 2
ZONE 1
LA
XRV
ZONE 4
Chapter 4
Line distance
R
RLoad
RF
99000189.vsd