ABB REL 501-C1 2.5 Technical Reference Manual page 30

Line distance protection terminal
Table of Contents

Advertisement

18
Terminal identification rated and base values
Parameter
Range
U3Scale
1.000 -
20000.000
Step: 0.001
Name_U3
0 - 13
U4b
30.000 -
500.000
Step: 0.001
U4Scale
1.000 -
20000.000
Step: 0.001
Name_U4
0 - 13
U5b
30.000 -
500.000
Step: 0.001
U5Scale
1.000 -
20000.000
Step: 0.001
Name_U5
0 - 13
Path in local HMI: Configuration/AnalogInputs/TrafoinpModule
Table 8:
Rated Currents
Parameter
Range
Ir *
0.1000 -
10.0000
Step: 0.0001
I1r *
0.1000 -
10.0000
Step: 0.0001
I2r *
0.1000 -
10.0000
Step: 0.0001
I3r*
0.1000 -
10.0000
Step: 0.0001
I4r*
0.1000 -
10.0000
Step: 0.0001
I5r*
0.1000 -
10.0000
Step: 0.0001
*) Setting can be done through the local HMI only. The setting should normally not be changed by the user.
The setting is factory preset and depends on the selected transformer input module.
Default
Unit
Description
2000.000
-
Main voltage transformer ratio, input U3
U3
char
User-defined name of input U3
63.509
V
Base voltage of input U4
2000.000
-
Main voltage transformer ratio, input U4
U4
char
User-defined name of input U4
63.509
V
Base voltage of input U5
2000.000
-
Main voltage transformer ratio, input U5
U5
char
User-defined name of input U5
Default
Unit
1.0000
A
1.0000
A
1.0000
A
1.0000
A
1.0000
A
1.0000
A
Chapter 2
General
Description
Rated current of transformer mod-
ule
Rated current of transformer on
input I1
Rated current of transformer on
input I2
Rated current of transformer on
input I3
Rated current of transformer on
input I4
Rated current of transformer on
input I5