1.5.4
1.5.5
1.5.6
Serial communication
Function block
ICOM-
IEC870-5-103
FUNCTYPE
ARBLOCK
OPFNTYPE
ZCOMBLK
BLKFNBLK
LEDRS
SETG1
SETG2
SETG3
SETG4
BLKINFO
xx00000225.vsd
Input and output signals
Table 188: Input signals for the IEC (ICOM-) function block
Signal
FUNCTYPE
OPFNTYPE
Path in local HMI: ServiceReport/Functions/IEC103Command
Table 189: Output signals for the IEC (ICOM-) function block
Signal
ARBLOCK
ZCOMBLK
BLKFNBLK
LEDRS
SETG1
SETG2
SETG3
SETG4
BLKINFO
Setting parameters
Table 190: Setting parameters for the IEC (ICOM-) function block
Parameter
Range
FuncType
0-255
OpFnType
Off, On
Description
Main function type for terminal
Main function type operation for terminal
Description
Command used for switching autorecloser on/off.
Command used for switching teleprotection on/off.
Command used for switching protection on/off.
Command used for resetting the LEDs.
Command used for activation of setting group 1.
Command used for activation of setting group 2.
Command used for activation of setting group 3.
Command used for activation of setting group 4.
Output activated when all information sent to master is blocked.
Default
Unit
0
-
Off
-
Chapter 12
Data communication
Description
Main function type for terminal
Set from CAP 540
Main function type operation for terminal
Set from CAP 540
191