Binary I/O Capabilities; Application; Technical Data - ABB REL 501-C1 2.5 Technical Reference Manual

Line distance protection terminal
Table of Contents

Advertisement

4
4.1
4.2

Binary I/O capabilities

Binary I/O capabilities

Application

Input channels with high EMI immunity can be used as binary input signals to any function. Sig-
nals can also be used in disturbance or event recording. This enables extensive monitoring and
evaluation of the operation of the terminal and associated electrical circuits.

Technical data

Table 212: BIM, PSM - Binary inputs
Inputs
Binary inputs
Debounce frequency
Oscillating signal discriminator.* Blocking and release settable between 1-40 Hz
Binary input voltage RL
Power dissipation (max.)
*) Only available for BIM
Table 213: BOM, PSM - Binary outputs
Function or quantity
Binary outputs
Max system voltage
Test voltage across open contact, 1 min
Current carrying capacity Continuous
1 s
Making capacity at
0.2 s
inductive load with
1.0 s
L/R>10 ms
Breaking capacity for AC, cos ϕ >0.4
Breaking capacity for DC with L/R<40ms
Maximum capacitive load
Power consumption for each output relay
RL24
RL48
BIM: 16, PSM: 4
5 Hz (BIM),
24/30 VDC
48/60 VDC
+/-20%
+/-20%
0.05 W/input
0.1 W/input
Trip and Signal relays
BOM: 24, PSM: 4
250 V AC, DC
1000 V rms
8 A
10 A
30 A
10 A
250 V/8.0 A
48 V/1 A
110 V/0.4 A
220 V/0.2 A
250 V/0.15 A
-
≤ 0.15 W
Chapter 13
Hardware modules
RL110
RL220
110/125 VDC
220/250 VDC
+/-20%
+/-20%
0.2 W/input
0.4 W/input
Fast signal relays
250 V AC, DC
800 V DC
8 A
10 A
0.4 A
0.4 A
250 V/8.0 A
48 V/1 A
110 V/0.4 A
220 V/0.2 A
250 V/0.15 A
10 nF