General fault criteria (GFC)
Table 97:
Setting parameters for the underimpedance operating mode (I
5 for I
= 5A)
r
Parameter
Range
Operation Z<
Off/On
ARGLd
5-45
Step: 1
RLd
0.10-400.00
Step: 0.01
X1RvPP
0.10-400.00
Step: 0.01
X1FwPP
0.10-400.00
Step: 0.01
RFPP
0.10-400.00
Step: 0.01
X1RvPE
0.1-400.00
Step: 0.01
X1FwPE
0.1-400.00
Step: 0.01
X0FwPE
0.1-1200.00
Step: 0.01
X0RvPE
0.1-1200.00
Step: 0.01
RFPE
0.1-400.00
Step: 0.01
Default
Unit
Description
Off
-
Operation of underimpedance based
GFC measurement enabled or disabled
25
degrees
Load angle determining the load imped-
ance area
50
ohm/loop
Limitation of resistive reach within the
load impedance area
50
ohm/phas
Positive sequence reactive reach in
e
reverse direction for phase-to-phase
faults
50
ohm/phas
Positive sequence reactive reach in for-
e
ward direction for phase-to-phase faults
50
ohm/loop
Resistive reach (forward and reverse) for
phase-to-phase measurement
50
ohm/phas
Positive sequence reactive reach in
e
reverse direction for phase-to-earth faults
50
ohm/phas
Positive sequence reactive reach in for-
e
ward direction for phase-to-earth faults
50
ohm/phas
Zero sequence reactance of reach in for-
e
ward direction for phase-to-earth faults
50
ohm/phas
Zero sequence reactance of reach in
e
reverse direction for phase-to-earth faults
50
ohm/loop
Resistive reach (forward and reverse) for
phase-to-earth measurement