Supervision of AC input quantities (DA)
Parameter
Range
RepInt
0-3600
Step: 1
EnDeadB
Off, On
DeadBand
0.0-99.9
Step: 0.1
EnIDeadB
Off, On
IDeadB
0.0-99.9
Step: 0.1
EnDeadBP
Off, On
Operation
Off, On
Hysteres
0.0-9999.9
Step: 0.1
EnAlRem
Off, On
EnAlarms
Off, On
HiAlarm
0.0-9999.9
Step: 0.1
HiWarn
0.0-9999.9
Step: 0.1
LowWarn
0.0-9999.9
Step: 0.1
LowAlarm
0.0-9999.9
Step: 0.1
RepInt
0-3600
Step: 1
EnDeadB
Off, On
DeadBand
0.0-9999.9
Step: 0.1
EnIDeadB
Off, On
IDeadB
0.0-9999.9
Step: 0.1
Default
Unit
Description
0
s
Time between reports for f in seconds. Zero
= Off (duration of time interval between two
reports at periodic reporting function. Setting
to 0 disables the periodic reporting)
Off
-
Enable amplitude dead band supervision for
f
1.0
Hz
Amplitude dead band for f
Off
Enable integrating dead band supervision for
f
5
Hz
Integrating dead band for f
Off
-
Enable periodic dead band reporting f
Apparent power measuring channel S:
DA16-
Off
-
Operating mode for DAnn function
5.0
MVA
Alarm hysteresis for S
On
-
Immediate event when an alarm is disabled
for S (produces an immediate event at reset
of any alarm monitoring element, when On)
Off
-
Set to 'On' to activate alarm supervision for S
(produces an immediate event at operation
of any alarm monitoring element, when On)
300.0
MVA
High Alarm level for S
200.0
MVA
High Warning level for S
80.0
MVA
Low Warning level for S
50.0
MVA
Low Alarm level for S
0
s
Time between reports for S in seconds. Zero
= Off (duration of time interval between two
reports at periodic reporting function. Setting
to 0 disables the periodic reporting)
Off
-
Enable amplitude dead band supervision for
S
1.0
MVA
Amplitude dead band for S
Off
-
Enable integrating dead band supervision for
S
10.0
MVA
Integrating dead band for S
Chapter 11
Monitoring