ABB REL 501-C1 2.5 Technical Reference Manual page 185

Line distance protection terminal
Table of Contents

Advertisement

Supervision of AC input quantities (DA)
Table 174: Setting parameters for the AC monitoring (DAnn-) function block
Parameter
Range
Operation
Off, On
Hysteres
0.0-1999.9
Step: 0.1
EnAlRem
Off, On
EnAlarms
Off, On
HiAlarm
0.0-1999.9
Step: 0.1
HiWarn
0.0-1999.9
Step: 0.1
LowWarn
0.0-1999.9
Step: 0.1
LowAlarm
0.0-1999.9
Step. 0.1
RepInt
0-3600
Step: 1
EnDeadB
Off, On
DeadBand
0.0-1999.9
Step: 0.1
EnIDeadB
Off, On
IDeadB
0.0-1999.9
Step: 0.1
EnDeadBP
Off, On
Operation
Off, On
Hysteres
0-99999
Step: 1
EnAlRem
Off, On
Default
Unit
Description
For each voltage input channels U1 - U5:
DA01--DA05
Off
-
Operating mode for DAnn function
5.0
kV
Alarm hysteres for U1 - U5
On
-
Immediate event when an alarm is disabled
for U1 - U5 (produces an immediate event at
reset of any alarm monitoring element, when
On)
On
-
Set to 'On' to activate alarm supervision for
U1 - U5 (produces an immediate event at
operation of any alarm monitoring element,
when On)
220.0
kV
High Alarm level for U1 - U5
210.0
kV
High Warning level for U1 - U5
170.0
kV
Low Warning level for U1 - U5
160.0
kV
Low Alarm level for U1 - U5
0
s
Time between reports for U1 - U5 in sec-
onds. Zero = Off (duration of time interval
between two reports at periodic reporting
function. Setting to 0 disables the periodic
reporting)
Off
-
Enable amplitude dead band supervision for
U1 - U5
5.0
kV
Amplitude dead band for U1 - U5
Off
-
Enable integrating dead band supervision for
U1 - U5
10.0
kV
Integrating dead band for U1 - U5
Off
-
Enable periodic dead band reporting U1 - U5
For each current input channels I1 - I5:
DA06 - DA10
Off
-
Operating mode for DAnn function
50
A
Alarm hysteresis for I1 - I5
On
-
Immediate event when an alarm is disabled
for I1 - I5 (produces an immediate event at
reset of any alarm monitoring element, when
On)
Chapter 11
Monitoring