Mains Supply; Motor Output And Torque Characteristics; Motor Output (U, V, W); Torque Characteristics - Danfoss VLT FC 103 Operating Manual

Refrigeration drive 355-800 kw, enclosure sizes e1h-e4h
Hide thumbs Also See for VLT FC 103:
Table of Contents

Advertisement

Operating Guide | VLT® Refrigeration Drive FC 103
FC 103
Fan power card overtemperature trip [°C (°F)]
Active in-rush card overtemperature trip [°C (°F)]
1
9.7 Fuses
For fuse ratings, see
.
2
Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions.) These values are based on a typical motor
efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for dimensioning of drive cooling. If the switching frequency is higher than the default
setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/
vltenergyefficiency. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W.
3
Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy efficiency class, see
Conditions
. For part load losses, see www.danfoss.com/vltenergyefficiency.

9.2 Mains Supply

The unit is suitable for use on a circuit capable of delivering not more than 100 kA short circuit current rating (SCCR) at 480/600 V.
Supply terminals
(1)
Supply voltage
Supply frequency
Maximum imbalance temporary between mains phases
True power factor (λ)
Displacement power factor (cos Φ)
Switching on the input supply L1, L2, and L3 (power-ups)
Environment according to EN 60664-1
1
Mains voltage low/mains drop-out: During low mains voltage or a mains drop-out, the drive continues until the DC-link voltage drops below the minimum stop level, which
corresponds typically to 15% below the drive's lowest rated supply voltage. Power-up and full torque cannot be expected at mains voltage lower than 10% below the drive's lowest
rated supply voltage.
2
Calculations based on UL/IEC 61800-3.

9.3 Motor Output and Torque Characteristics

9.3.1 Motor Output (U, V, W)

Voltage output
Output frequency
Output frequency in flux mode
Switching on output
Ramp times
1
Dependent on voltage and power.

9.3.2 Torque Characteristics

The torque response time depends on application and load but as a rule, the torque step from 0 to reference is 4–5 x torque rise time.
132 | Danfoss A/S © 2020.01
N630
N710
85 (185)
85 (185)
85 (185)
85 (185)
380–480/500 V ±10%, 525–690 V ±10%
Overvoltage category III/pollution degree 2
AQ275652766279en-000101 / 130R0707
Specifications
N800
85 (185)
85 (185)
9.4 Ambient
L1, L2, L3
50/60 Hz ±5%
3.0% of rated supply voltage
≥0.9 nominal at rated load
Near unity (>0.98)
Maximum 1 time/2 minutes
0–100% of supply voltage output
0–590 Hz
0–300 Hz
Unlimited
0.01–3600 s
(2)
(1)