Read On Init Delay; Time Telegram Rate - ABB i-bus KNX MG/S 11.100.1.1 Product Manual

Modbus rtu, knx tp gateway
Table of Contents

Advertisement

ABB i-bus
®
KNX
Parameters
7.2.1.1

Read On Init Delay

This parameter is used to define the sending delay of the GroupValueRead telegram for Group Objects
with an initialization flag "I".
Note
I flag:
If the device is reset, a new GroupValueRead telegram is sent after the device restarts. The purpose of
this is to call the object value via a GroupValueResponse. Reasons for a device reset are a power failure
and subsequent bus voltage recovery, an explicit device reset, or an ETS download.
Explanation on knx.org ->
Option
0...255 s
Prerequisites for visibility
7.2.1.2

Time Telegram Rate

This parameter is used to define the waiting time between two telegrams before they are sent on the bus
(ABB i-bus
parameter. This limit relates to all telegrams sent by the device.
Option
0...5000 ms
Prerequisites for visibility
Note about navigation in the PDF: Key combination
'Alt + left arrow' jumps to the previous view/page
KNX flags
This parameter is in the General parameter window.
®
KNX). The bus load generated by the device can be limited using the Time Telegram Rate
This parameter is in the General parameter window.
Product Manual | EN | MG/S 11.100.1.1 | 9AKK108467A5941 Rev. B 31