Response Timeout; Interframe Timeout - ABB i-bus KNX MG/S 11.100.1.1 Product Manual

Modbus rtu, knx tp gateway
Table of Contents

Advertisement

ABB i-bus
®
KNX
Parameters
7.2.1.7

Response Timeout

This parameter defines how many milliseconds the gateway waits between sending a request to a server
and receiving a response.
If the gateway receives a response before this time elapses, it resets the timer and continues polling.
If the gateway does not receive a response, it re-sends the request. The gateway repeats the request
three times before reporting the error via the corresponding Error Status Group Objects.
Option
100 ... 1000 ... 2000 ms
Note
Some servers have long processing times. This information is usually provided in the server manual.
Take this into account when setting the Response Timeout parameter.
Prerequisites for visibility
7.2.1.8

Interframe Timeout

This parameter defines how many milliseconds the gateway waits between receiving and sending a
Modbus telegram. The Modbus load generated by the device can be limited using the Interframe Timeout
parameter. This limit relates to all Modbus telegrams sent by the device.
Option
0 ... 60 ... 10000 ms
Prerequisites for visibility
34 9AKK108467A5941 Rev. B | MG/S 11.100.1.1 | EN | Product Manual
This parameter is in the General parameter window.
This parameter is in the General parameter window.
Note about navigation in the PDF: Key combination
'Alt + left arrow' jumps to the previous view/page

Advertisement

Table of Contents
loading

Table of Contents