7.2.1.7
Response Timeout
This parameter defines how many milliseconds the gateway waits between sending a request to a server
and receiving a response.
If the gateway receives a response before this time elapses, it resets the timer and continues polling.
If the gateway does not receive a response, it re-sends the request. The gateway repeats the request
three times before reporting the error via the corresponding Error Status Group Objects.
Option
100 ... 1000 ... 2000 ms
Note
Some servers have long processing times. This information is usually provided in the server manual.
Take this into account when setting the Response Timeout parameter.
Prerequisites for visibility
7.2.1.8
Interframe Timeout
This parameter defines how many milliseconds the gateway waits between receiving and sending a
Modbus telegram. The Modbus load generated by the device can be limited using the Interframe Timeout
parameter. This limit relates to all Modbus telegrams sent by the device.
Option
0 ... 60 ... 10000 ms
Prerequisites for visibility