ABB i-bus
®
KNX
Parameters
7.2.2.15
# Bits
This parameter is used to define the number of specific bits in the assigned register.
The options in the # Bits parameter are only adjustable when the Format:4: BitFields option is selected.
Option
1 ...x ... 15... -
Note
The Bit parameter defines the start bit within the data point in the assigned register.
Prerequisites for visibility
7.2.2.16
Deadband
This parameter defines the minimum (absolute) value change of the Modbus data before the new value is
written to the associated Status Group Object. This avoids excessive sending when making minimal value
changes.
Option
0 ... 100
Note
When calculating the Device x Deadband parameter, always take account of the type and resolution of
the Modbus data points.
Example
The Modbus server stores the voltage value of 230 V as 2300 in the Modbus register. For a minimum
change in value (absolute value) of 0.5 V, the deadband should be set to 5.
Prerequisites for visibility
50 9AKK108467A5941 Rev. B | MG/S 11.100.1.1 | EN | Product Manual
•
This parameter is in the Config Device x parameter window.
This parameter is in the Config Device x parameter window.
•