Group Objects; Summary Of Group Objects - ABB i-bus KNX SUG/U 1.1 Product Manual

Split unit
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
3.3

Group objects

3.3.1

Summary of group objects

No.
Function
1
In operation
2
Request Status values
3
Fan speed
4
Status Fan speed
5
Fan up/down
6
Operation mode
7
Status Operating mode
8
Simplified Mode
9
Silent Mode
10
Status Silent Mode
11
Scene
12
On/Off
13
Status On/Off
14
Deactivate On/Off delay
15
Forced operation
16
Status Forced operation
17
Window contact
18
Status Window contact
19
Presence
20
Status Presence
21
Setpoint temperature
22
Status Setpoint temperature
23
Setpoint temperature up/down
24
Deactivate Setpoint temperature limit
25
Vertical Swing
26
Status Vertical swing
27
Horizontal Swing
28
Status Horizontal swing
29
Boost
30
Status Boost
36 2CDC508171D0201 | SUG/U 1.1
Name
General
General
Split unit
Split unit
Split unit
Split unit
Split unit
Split unit
Split unit
Split unit
Function
Split unit
Split unit
Split unit
Function
Function
Function
Function
Function
Function
Split unit
Split unit
Split unit
Split unit
Split unit
Split unit
Split unit
Split unit
Function
Function
Data Point
Length
Type (DPT)
1.002
1 bit
1.017
1 bit
5.001
1 byte
5.010
5.001
1 byte
5.010
1.007
1 bit
20.105
1 byte
20.105
1 byte
1,100
1 bit
1.002
1 bit
1.002
1 bit
18.001
1 byte
1.001
1 bit
1.001
1 bit
1.003
1 bit
1.003
1 bit
1.003
1 bit
1.019
1 bit
1.019
1 bit
1.018
1 bit
1.018
1 bit
9.001
2 byte
9.001
2 byte
1.007
1 bit
1.003
1 bit
1.001
1 bit
1.001
1 bit
1.001
1 bit
1.001
1 bit
1.001
1 bit
1.001
1 bit
Flags
C
L
W T
R
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

Advertisement

Table of Contents
loading

Table of Contents