Foundation ™ Fieldbus (Output Option Code F) - Emerson Rosemount 5402 Reference Manual

Level transmitter, two-wire non-contacting radar
Hide thumbs Also See for Rosemount 5402:
Table of Contents

Advertisement

Specifications and Reference Data
October 2018
Explosion-Proof/Flameproof Installations:
Maximum Load Resistance R(
1400
1200
1148
1000
800
600
400
348
200
24
10
20
Note
The diagram is only valid if the HART load resistance is at the
+ side and if the - side is grounded, otherwise the load
resistance value is limited to 435 .
A.1.3 F
OUNDATION
option code F) Output
6200 ft (1900 m) max
(depending upon cable
characteristics)
H1 - Low Speed
Field Bus
Fieldbus
modem
PC with Rosemount
Radar Master
Rosemount 752 Field
Signal Indicator
Rosemount
5601
Rosemount
5401
Rosemount
5301
Field Communicator
207
)
Operating
region
42.4
30
40
External Power Supply Voltage U
Fieldbus (output
H2 - High Speed
Field Bus
Maintenance
Host/DCS system
(e.g. DeltaV
Signal wiring
Recommended output cabling is twisted shielded pairs,
18-12 AWG
External power supply
The input voltage UI for F
(9-30 Vdc in IS applications, 9-17.5 Vdc in FISCO
applications, and 16-32 Vdc in Explosion-proof/flameproof
50
(V)
applications).
E
Quiescent current draw
21 mA
F
OUNDATION
execution time
Block
1 Resource
3 Transducer
6 Analog input (AI)
1 Proportional/Integral/Derivate
(PID)
1 Control selector (CS)
1 Output splitter (OS)
1 Signal Characterizer (SC)
1 Integrator (IT)
1 Arithmetic (AR)
1 Input selector (IS)
F
OUNDATION
Master)
Link Master (LAS)
Conforming F
ITK 6.1.1
F
OUNDATION
)
Plantweb
Alerts
Reference Manual
00809-0100-4026, Rev KC
Fieldbus is 9-32 Vdc
OUNDATION
Fieldbus blocks and
Execution time
N/A
N/A
10 ms
15 ms
10 ms
10 ms
10 ms
10 ms
10 ms
10 ms
Fieldbus class (Basic or Link
Fieldbus
OUNDATION
Fieldbus alerts
Specifications and Reference Data

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rosemount 5401Rosemount 5400

Table of Contents