Troubleshooting Overview - Emerson Rosemount 5402 Reference Manual

Level transmitter, two-wire non-contacting radar
Hide thumbs Also See for Rosemount 5402:
Table of Contents

Advertisement

Reference Manual
00809-0100-4026, Rev KC
7.2

Troubleshooting overview

Table 7-1
symptoms and necessary actions to be taken.
Table 7-1. Troubleshooting Chart
Symptom
No level reading
®
No HART
communication
Analog Out is set in
Alarm
Incorrect level reading
Integral display does not
work
Temperature
measurement failure
Level measurement
failure
Volume measurement
failure
No surface echo
1.
A malfunctioning display panel may only be replaced by service personnel at the Emerson Automation Solutions Service Department.
2.
If the Rosemount 5400 has been exposed to temperatures outside the specified limits, the device may stop its normal operation.
Service and Troubleshooting
below gives information on the possible causes of system malfunctions. It also lists the
Possible cause
Power disconnected
Data communication cables
disconnected
COM Port configuration does not
match the connected COM Port
Cables may be disconnected
Wrong HART address is used
Hardware failure
HART resistor
Measurement failure or
transmitter failure
Configuration error
Disturbing objects in the tank
See
"Application errors" on
page 187
Action
Check the power supply.
Check the cables for serial data communication.
Check LED/Display.
Check that correct COM Port is selected in the HART server .
See
"Specifying the COM port" on page
Check the COM port buffer,
page 112
.
Check wiring diagram.
Verify that the 250  resistor is in the loop. See
page 97
.
Check cables.
Make sure that correct HART short address is used.
Try address = 0
Check the COM Port Buffer setting, see page
port buffers" on page 113
Check Analog Output current value to verify that transmitter
hardware works.
Open the Diagnostics window in RRM to check active errors and
alarms, see
"Diagnostics" on page
See also
"Analyzing the measurement signal" on page 162
"Analog Output status" on page 186
Check the Tank Height parameter; RRM>Setup>Tank.
Check status information and diagnostics information, see
"Diagnostics" on page 174
Check that the transmitter has not locked on an interfering object.
See
"Analyzing the measurement signal" on page 162
Check the display configuration in RRM (open menu Setup >
General).
Diagnostics
Contact Emerson Automation Solutions Service Department
Check ambient temperature
Restart gauge.
Contact Emerson Automation Solutions Service Department.
Check Power Supply.
Check the gauge configuration.
Check that the mechanical installation is correct.
Restart gauge.
Check gauge configuration using PC Based configuration tool.
Check signal strength.
Restart transmitter.
See
"Analyzing the measurement signal" on page 162
Service and Troubleshooting