Service and Troubleshooting
October 2018
190
The level value drops to a
lower value when the
product surface is close to
the antenna.
The transmitter displays
"measurement error" and
activates Measurement
Alarm
Alarm when the product
level is close to the antenna.
The measured level is
unstable.
Reference Manual
00809-0100-4026, Rev KC
May be caused by:
Product level within the Hold Off region, that
is outside the approved measuring range, and
the transmitter is picking up secondary signal
reflections
Action:
Avoid filling the tank to levels close to the
antenna.
Move the transmitter to increase the distance
between maximum product level and
antenna, if possible.
Activate the Full Tank Handling function if
measurements up to the antenna are
required, see
"Full tank handling" on
page 261
and
267.
May be caused by:
Product level within the Hold Off region, that
is outside the approved measuring range
Action:
Avoid filling the tank to levels very close to the
antenna.
Move the transmitter to increase the distance
between maximum product level and
antenna, if possible.
Activate the Full Tank Handling function if
measurements up to the antenna are
required, see
"Full tank handling" on
page 261
and
267.
May be caused by:
An empty tank with the Amplitude Threshold
too low
Product surface is close to a registered False
Echo
Action:
Create a new ATC, see
"Echo tuning" on
page 109.
Service and Troubleshooting