Emerson Rosemount 5402 Reference Manual page 133

Level transmitter, two-wire non-contacting radar
Hide thumbs Also See for Rosemount 5402:
Table of Contents

Advertisement

Reference Manual
00809-0100-4026, Rev KC
Digital units
5. The Length Unit, Level Rate Unit, Volume Unit, and Temperature Unit information is entered in this window.
Tank geometry
6. Set the tank geometry parameters.
Select the Tank Type corresponding to the actual tank. If none of the available options matches the tank, select
Unknown.
HART command: [2, 1, 2, 1].
F
OUNDATION
TRANSDUCER_1100 > GEOM_TANK_TYPE.
Tank Bottom Type is important for the measurement performance close to the tank bottom.
HART command: [2, 1, 2, 2].
F
OUNDATION
TRANSDUCER_1100 > GEOM_TANK_BOTTOM_TYPE.
Tank Height is the distance from the Upper Reference Point to the Lower Reference Point (see
on page
HART command: [2, 1, 2, 3].
F
OUNDATION
TRANSDUCER_1100 > GEOM_TANK_HEIGHT.
Configuration
Fieldbus parameter:
Fieldbus parameter:
101). This number needs to be as accurate as possible.
Fieldbus parameter:
Configuration
October 2018
"Tank geometry"
119