Service and Troubleshooting
October 2018
7.14.3

Errors

Error messages that may be displayed on the Integral Display, on a Field Communicator, in AMS Suite, or
in the RRM program, are shown in
Errors are indicated in RRM in the Diagnostics window.
Table 7-3. Error Messages
Message
RAM Error
FPROM Error
HREG Error
MWM Error
Display Error
Modem Error
Analog Out Error
Internal Temp Error
Other HW Error
Meas Error
Config Error
SW Error
182
Table
7-3. Errors normally result in an Analog Output alarm.
Description
An error in the gauge data memory
(RAM) has been detected during the
startup tests.
NOTE: this resets the gauge
automatically.
An error in the gauge program
memory (FPROM) has been
detected during the startup tests.
NOTE: this resets the gauge
automatically.
An error in the transmitter
configuration memory (EEPROM)
has been detected. The error is
either a checksum error that can be
solved by loading the default
database or a hardware error.
NOTE: the default values are used
until the problem is solved.
An error in the microwave module.
An error in the LCD display.
Modem hardware failure.
An error in the Analog Out Module.
An error in internal temperature
measurement.
An unspecified hardware error has
been detected.
A serious measurement error has
been detected.
At least one configuration
parameter is outside the allowed
range.
NOTE: the default values are used
until the problem is solved.
An error has been detected in the
transmitter software.
Reference Manual
00809-0100-4026, Rev KC
Action
Contact Emerson Automation Solutions
Service Department.
Contact Emerson Automation Solutions
Service Department.
Load default database and restart the
transmitter. Contact Emerson
Automation Solutions Service
Department if the problem persists.
Contact Emerson Automation Solutions
Service Department.
Contact Emerson Automation Solutions
Service Department.
Contact Emerson Automation Solutions
Service Department.
Contact Emerson Automation Solutions
Service Department.
Contact Emerson Automation Solutions
Service Department.
Contact Emerson Automation Solutions
Service Department.
Contact Emerson Automation Solutions
Service Department.
Load the default database and restart the
transmitter (see
"Reset to factory
settings" on page
177)
Configure the transmitter or upload a
backup configuration file (see
up the transmitter configuration" on
page
173)
Contact Emerson Automation Solutions
Service Department if the problem
persists
Contact Emerson Automation Solutions
Service Department.
Service and Troubleshooting