Specifications - Redback SH5000 Installation Manual

Smart hybrid system, inverter, battery enclosure
Hide thumbs Also See for SH5000:
Table of Contents

Advertisement

Specifications

Specifications
PV PORT
Number of MPPTs
Strings per MPPT Input
MPPT Operating Voltage (range)
MPPT Full Load (range)
Maximum Input Voltage (Vmax)
Maximum Current (Imp)
Short Circuit Current (Isc)
Maximum Feedback Current
Decisive Voltage Class (DVC)
GRID INTERACTIVE PORT
Nominal Output Voltage
Nominal Output Frequency
Rated Output Current
Max. Output Current
Rated Output Active Power
Rated Output Apparent Power
Rated Input Current
Rated Input Apparent Power
Power Factor (range)
Output Voltage THD
Inrush Current
Maximum Output Fault Current
Maximum Output Overcurrent Protection
Decisive Voltage Class (DVC)
BACKUP PORT
Nominal Output Voltage
Nominal Output Frequency
Rated Current
Rated Active Power
Rated Apparent Power
Peak Apparent Power
Power Factor (range)
Output Voltage THD
Inrush Current
Maximum Output Fault Current
Maximum Output Overcurrent Protection
Decisive Voltage Class (DVC)
BATTERY PORT
Voltage (nominal)
Max. Current (charge)
Max. Power (charge)
Max. Current (discharge)
Max. Power (charge)
Battery Type
Battery Depth of Discharge
Short Circuit Current
Decisive Voltage Class (DVC)
58
Installation Manual - Redback Smart Hybrid System - v2.0
VERSION 022x
2
1/1
DC 125 - 550V
DC 215 – 500V
DC 580V
DC 11/11A
DC 13.8/13.8A
0A
DVC-C
ALL VERSIONS
AC 230V
50 Hz
AC 21.7A
AC 24.5A
AC 5000W
5000VA
AC 40A
9200VA
0.8 lagging to 0.8 leading
<4.5%
60A,3 µs
43A,0.2s
60A,3 µs
DVC-C
AC 230V
50 Hz
AC 20A
AC 4600W
4600VA
6900VA (10 sec max)
0.8 lagging to 0.8 leading
<4.5%
55A, 2µs
43A, 10s
30A
DVC-C
DC 40 - 60V
DC 90 A
DC 4600W
DC 100A
DC 4600W
Li-ion
90%
1600A
DVC-A
VERSION 024x
2
1/1
DC 125 - 550V
DC 190 - 500V
DC 580V
DC 14/14A
DC 17.5/17.5A
0A
DVC-C

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Be14000

Table of Contents