3.5

Notes on regional settings

Regional Safety Setting is a mandatory selection when configuring the system—the system will not operate if it is not selected.
You may be prompted to update the inverter software. Do this if requested.
For convenience the Regional Safety Settings are set by selecting the Region from the list provided in the RedbackINSTALL app.
The list is maintained with the latest settings required by AS4777.2:2020. Selection of a region automatically selects Power
Quality Response Mode settings, including:
• Voltage balance mode (where available)
• Voltage and frequency limits
• Sustained operation for frequency variations
• Grid Protection
• Power Rate Limits
• Frequency Response Limits
• Voltage Disturbance Band Withstand
• Volt-Var response
• Volt-Watt response
• Fixed Power Factor Mode
• Reactive Power mode
INFORMATION. The local grid operator may request a non-standard safety setting for an installation. To adjust
power quality response mode setpoints from default values please contact Redback Technical Support.