Lay the cables carrying current separately and with a distance of at least 15 cm from the
communication cables.
Note
Installer is responsible for calculation and design
The installer is responsible for calculating and implementing the connection.
Connection of the charging station must comply with standards and regulations.
Table 4-3
Suggested cable cross-sections
Area
Supply line
Charging station - Dispenser
Charging station - Dispenser
Charging station - Dispenser
Charging station - Dispenser
Charging station - Dispenser
The cable cross-sections relate to the installation type "Installation type in ground".
SICHARGE UC 100, UC 200, UC 300, UC 400, UC 600, UC 800
Operating Instructions, 10/2022, A5E50828019-AC
Function
AC400V connection
DC750V connection
DC750V connection
Grounding
AC230V-AUX supply
Communication
4.4 Application planning of UC 300/400
UC 300/400 charging
station
L1/L2/L3/PE
2 x 4 x 95 mm²
L+
2 x 1 x 70 mm²
L-
2 x 1 x 70 mm²
PE
1 x 1 x 35 mm²
L/N/PE
1 x 3 x 2.5 mm²
 
RJ45 CAT 6 (TP)
F.O. 50/125, OM4,
4 fib.
Application planning
Cable type
0.6/1.0kV, Cu/
XLPE/AWA/PVC
0.6/1.0kV, Cu/
XLPE/AWA/PVC
0.6/1.0kV, Cu/
XLPE/AWA/PVC
Cu/PVC (Y/G)
0.3/0.5 kV,Cu/PVC
LIYCY (TP)
61