DIQ/S 281
Materials required
Tools
ba76226e02
3.9
Connections to the relay and current outputs
3.9.1 General installation instructions
WARNING
If external electrical circuits that are subject to the danger
of physical contact are incorrectly connected to the relay
contacts, there may be a danger of life threatening electric
shock. Electrical circuits are regarded to be subject to the
danger of physical contact when there are voltages higher
than the Safety Extra Low Voltage (SELV).
Pay attention to the following points during installation:
Electrical circuits subject to the danger of physical
Electrical circuits subject to the danger of physical
If electrical circuits subject to the danger of physical
Switching voltages and switching currents on the relay
Only single-phase consumers can be switched with the
After the Universal Transmitter DIQ/S 281 has been in-
Wire end sleeves, suitable for the connecting wires, with suitable crimping
tool
4 x cable gland with sealing ring (scope of delivery of the DIQ/S 281)
Cable stripping knife
Wire stripper
Phillips screwdriver
Small screwdriver
03/2023
contact may only be connected by a qualified electri-
cian.
contact may only be connected when they are voltage-
free.
contact are switched with a relay, no circuit that is not
subject to this danger (e. g. the DIQ/CHV module) may
be operated on the further relays.
contacts must not exceed the values specified in
chapter 9 T
ECHNICAL DATA
against currents that are too high with an electrical
fuse.
relays. Under no circumstances may multiphase con-
sumers be switched with the aid of several relays (ex-
ample: three-phase current driven pumps). Always
switch multiphase consumers via a protective relay.
stalled, it may only be opened if all external voltages
have been switched off beforehand.
. Protect electrical circuits
Installation
49