Propheatgx (Msv45) - Distech Controls ECLYPSE ECY-303 User Manual

Preloaded applications
Table of Contents

Advertisement

ID
Multi State Value 43

PropHeatGx (MSV45)

This variable is used to display the stage number of the proportional heating for the Envsyion graph-
ics.
ID
Multi State Value 45
ECY-303 Preloaded Applications
Enumeration
1 = Unconfig : The unit is not equipped with a humidifier
2 = Cool1 : The output is used to control cooling/compressor stage 1
3 = Cool2 : The output is used to control cooling/compressor stage 2
4 = Cool3 : The output is used to control cooling/compressor stage 3
5 = Cool4 : The output is used to control cooling/compressor stage 4
6 = Heat1 : The output is used to control heating stage 1
7 = Heat2 : The output is used to control heating stage 2
8 = Heat3 : The output is used to control heating stage 3
9 = Min Position : The output is used to control the minimum position of
the dampers
10 = Reversing Valve : The output is used to control the reversing valve
of a heat pump unit
11 = Prop Heating : The output is used to control a proportional heating
stage
12 = Dampers : The output is used to control the dampers
13 = Humidier : The output is used to control the humidifier
14 = Power Exhaust : The output is used to control a damper power
exhaust
Enumeration
1 = Stage1 : The proportional heating stage is the stage 1 of heating
2 = Stage2 : The proportional heating stage is the stage 2 of heating
3 = Stage3 : The proportional heating stage is the stage 3 of heating
4 = Unconfig : The proportional heating stage is not configured
Variables
Default Value
Unconfig
Default Value
Unconfig
43