Viewing The Wiring Guide - Distech Controls ECLYPSE ECY-303 User Manual

Preloaded applications
Table of Contents

Advertisement

Allure EC-Smart-Vue Screen-by-Screen Guide
Output Configuration Tables
Output (BACnet object
COOLHEAT STGS (MSV 32)
REV VLV (MSV 33)
PROP HT (MSV 34)
DAMPERS (MSV 35)
HUMIDIFIER (MSV 36)
ENABLE

Viewing the Wiring Guide

From the Allure EC-Smart-Vue's Wiring submenu, the correct wiring options can be viewed. Once the
Output Configuration is set, the Wiring submenu will indicate what needs to be wired to a particular
output number on the controller.
To enter the advanced menus:
1. Hold the Menu button for five seconds:
The password field appears.
2. Use the arrow keys to increase or decrease the displayed number until it matches the configured
password.
72
Default
Valid Choices
1
x
2
3
4
1
x
2
3
x
1
2
3
x
1
2
3
4
x
1
2
3
4
5
6
7
8
x
1
2
3
4
5
x
1
2
pm
°F
Parameter
Description
Cool
Cooling stages
Heat
Heating stages
Reversing valve is
Unconfig
unconfigured
Cooling
Reversing valve cooling
Heating
Reversing valve heating
Proportional heating is
Unconfig
unconfigured
Analog 0-10V
0 – 10 V analog signal
Analog 2-10V
2 – 10 V analog signal
PWM
Pulse width modulation
Unconfig
Dampers are unconfigured
Analog 0-10V
0 – 10 V analog signal
Analog 2-10V
2 – 10 V analog signal
0 – 10 V protected earth
Analog 0-10V PE
analog signal
2 – 10 V protected earth
Analog 2-10V PE
analog signal
EconEnable
Economizer enabled
Economizer & minimum
Econ & MinPos
damper position
Enable minimum damper
Min Pos Enable
position
Unconfig
Humidifier is unconfigured
Analog 0-10V
0 – 10 V analog signal
Analog 2-10V
2 – 10 V analog signal
PWM
Pulse width modulation
Digital
Digital signal
Enable
Enable output control
Disable
Disable output control
5 sec