Distech Controls ECLYPSE ECY-303 User Manual page 20

Preloaded applications
Table of Contents

Advertisement

Variables
ID
Analog Value 21
Dampers (AV22)
This variable is used to display the actual outside air dampers signal. This variable can be used to
override the outside air dampers control signal.
ID
Analog Value 22
OptStartMaxStartupTime (AV23)
This variable is used to configure the maximum startup time allowed before the occupied mode.
ID
Analog Value 23
OptStartFactorWeight (AV24)
This variable is used to configure the % of the new factor that will be taken into account to calculate
the new factor OptStartCoolFactor (AV14) or OptStartHeatFactor (AV15).
ID
Analog Value 24
CoolStgOnDelay (AV26)
This variable is used to configure the delay before starting any cooling stage.
ID
Analog Value 26
CoolStgOffDelay (AV27)
This variable is used to configure the delay before stopping any cooling stage.
ID
Analog Value 27
HeatStgOnDelay (AV28)
This variable is used to configure the delay before starting any heating stage.
ID
Analog Value 28
HeatStgOffDelay (AV29)
This variable is used to configure the delay before stopping any heating stage.
ID
Analog Value 29
DampersDischAirSP (AV30)
This variable is used to configure the minimum discharge temperature limit for the outside air dampers
control signal.
20
Units
Percent (%)
Units
Percent (%)
Units
minutes
Units
Percent (%)
Units
Seconds
Units
Seconds
Units
Seconds
Units
Seconds
Valid Range
0 to 100%
Valid Range
0 to 100%
Valid Range
N/A
Valid Range
1 to 100%
Valid Range
N/A
Valid Range
N/A
Valid Range
N/A
Valid Range
N/A
ECY-303 Preloaded Applications
Default Value
999%
Default Value
999%
Default Value
240 min
Default Value
10%
Default Value
180s
Default Value
120s
Default Value
180s
Default Value
120s