Variables
ID
Analog Value 37
UnoccCoolSp (AV38)
This variable is used to configure the cooling setpoint when the occupancy status (MSV15) is in unoc-
cupied mode.
ID
Analog Value 38
StandbyCoolSp (AV39)
This variable is used to configure the cooling setpoint when the occupancy status (MSV15) is in
standby mode.
ID
Analog Value 39
OccCoolSp (AV40)
This variable is used to configure the cooling setpoint when the occupancy status (MSV15) is in occu-
pied mode.
ID
Analog Value 40
OccHeatSp (AV41)
This variable is used to configure the heating setpoint when the occupancy status (MSV15) is in occu-
pied mode.
ID
Analog Value 41
StandbyHeatSp (AV42)
This variable is used to configure the heating setpoint when the occupancy status (MSV15) is in
standby mode.
ID
Analog Value 42
UnoccHeatSp (AV43)
This variable is used to configure the heating setpoint when the occupancy status (MSV15) is in unoc-
cupied mode.
ID
Analog Value 43
MinFanCurrent (AV44)
This variable is used to configure the minimum scaling of UI6 when configured for FanCurrent. The
range of the input can be configured using UI6Range(MSV20)
ID
Analog Value 44
22
Units
Degrees-Celsius (°C)
Units
Degrees-Celsius (°C)
Units
Degrees-Celsius (°C)
Units
Degrees-Celsius (°C)
Units
Degrees-Celsius (°C)
Units
Degrees-Celsius (°C)
Units
Degrees-Celsius (°C)
Units
Amperes (A)
Valid Range
N/A
Valid Range
N/A
Valid Range
N/A
Valid Range
N/A
Valid Range
N/A
Valid Range
N/A
Valid Range
N/A
Valid Range
N/A
ECY-303 Preloaded Applications
Default Value
N/A
Default Value
28°C
Default Value
26°C
Default Value
24°C
Default Value
21°C
Default Value
19°C
Default Value
17°C
Default Value
0 A