Specifications
Control card, 24 V DC output
Terminal number
Output voltage
Max. load
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital
inputs and outputs.
Relay outputs
Programmable relay outputs
Relay 01 Terminal number
Max. terminal load (AC-1)
Max. terminal load (AC-15)
Max. terminal load (DC-1)
Max. terminal load (DC-13)
Relay 02 Terminal number
Max. terminal load (AC-1)
Max. terminal load (AC-15)
Max. terminal load (DC-1)
Max. terminal load (DC-13)
Max. terminal load (AC-1)
8
8
Max. terminal load (AC-15)
Max. terminal load (DC-1)
Max. terminal load (DC-13)
Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO)
Environment according to EN 60664-1
1) IEC 60947 parts 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2) Overvoltage Category II
3) UL applications 300 V AC 2 A
Control characteristics
Resolution of output frequency at 0-1000 Hz
System response time (terminals 18, 19, 27, 29, 32, 33)
Speed control range (open loop)
Speed accuracy (open loop)
All control characteristics are based on a 4-pole asynchronous motor
84
Operating Instructions
1)
on 1-3 (NC), 1-2 (NO) (resistive load)
(inductive load @ cosφ 0.4)
1)
1)
on 1-2 (NO), 1-3 (NC) (resistive load)
1)
(inductive load)
1)
2)3)
on 4-5 (NO) (resistive load)
on 4-5 (NO) (inductive load @ cosφ 0.4)
1)
1)
on 4-5 (NO) (resistive load)
1)
on 4-5 (NO) (inductive load)
1)
on 4-6 (NC) (resistive load)
on 4-6 (NC) (inductive load @ cosφ 0.4)
1)
1)
on 4-6 (NC) (resistive load)
1)
on 4-6 (NC) (inductive load)
Danfoss A/S © Rev. 2014-01-22 All rights reserved.
24 V (+1, -3 v)
1-3 (break), 1-2 (make)
240 V AC, 0.2 A
24 V DC, 0.1 A
4-6 (break), 4-5 (make)
400 V AC, 2 A
240 V AC, 0.2 A
24 V DC, 0.1 A
240 V AC, 2 A
240 V AC, 0.2 A
24 V DC, 0.1 A
24 V DC 10 mA, 24 V AC 20 mA
overvoltage category III/pollution degree 2
1:100 of synchronous speed
30-4000 RPM: Maximum error of ±8 RPM
13
200 mA
2
240 V AC, 2A
60 V DC, 1 A
80 V DC, 2 A
50 V DC, 2 A
±0.003 Hz
≤ 2 ms
MG21B202
Need help?
Do you have a question about the VLT AQUA Drive FC 202 and is the answer not in the manual?
Questions and answers