Automatic Energy Optimisation (Aeo); Automatic Motor Adaptation (Ama); Checking Motor Rotation - Danfoss VLT AQUA Drive FC 202 Operating Instructions Manual

Low harmonic drive
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Commissioning
Application
Low inertia applications
I
/I
<5
Load
Motor
Low inertia applications
50>I
/I
>5
Load
Motor
High inertia applications
I
/I
> 50
Load
Motor
5
5
High load at low speed
<30% (rated speed)
Table 5.7 Recommendations in Different Applications
If the motor starts oscillating at a certain speed, increase
1-14 Damping Gain. Increase the value in small steps.
Depending on the motor, a good value for this parameter
can be 10% or 100% higher than the default value.
Starting torque can be adjusted in 1-66 Min. Current at Low
Speed. 100% provides nominal torque as starting torque.

5.4.5 Automatic Energy Optimisation (AEO)

NOTICE
AEO is not relevant for permanent magnet motors.
Automatic Energy Optimisation (AEO) is a procedure that
minimises voltage to the motor, reducing energy
consumption, heat, and noise.
To activate AEO, set parameter 1-03 Torque Characteristics
to [2] Auto Energy Optim. CT or [3] Auto Energy Optim. VT.

5.4.6 Automatic Motor Adaptation (AMA)

NOTICE
AMA is not relevant for PM motors.
Automatic motor adaptation (AMA) is a procedure that
optimises compatibility between the frequency converter
and the motor.
The frequency converter builds a mathematical
model of the motor for regulating output motor
current. The procedure also tests the input phase
balance of electrical power. It compares the
52
Operating Instructions
Settings
1-17 Voltage filter time const. to be
increased by factor 5 to 10
1-14 Damping Gain should be
reduced
1-66 Min. Current at Low Speed
should be reduced (<100%)
Keep calculated values
1-14 Damping Gain, 1-15 Low Speed
Filter Time Const. and 1-16 High
Speed Filter Time Const. should be
increased
1-17 Voltage filter time const. should
be increased
1-66 Min. Current at Low Speed
should be increased (>100% for a
prolonged time can overheat the
motor)
Danfoss A/S © Rev. 2014-01-22 All rights reserved.
motor characteristics with the data entered in
parameters 1-20 to 1-25.
The motor shaft does not turn and no harm is
done to the motor while running the AMA.
Some motors may be unable to run the complete
version of the test. In that case, select [2] Enable
reduced AMA.
If an output filter is connected to the motor,
select Enable reduced AMA.
If warnings or alarms occur, see
chapter 7 Diagnostics and Troubleshooting.
Run this procedure on a cold motor for best
results.
To run AMA
1.
Press [Main Menu] to access parameters.
2.
Scroll to parameter group 1-** Load and Motor
and press [OK].
3.
Scroll to parameter group 1-2* Motor Data and
press [OK].
4.
Scroll to 1-29 Automatic Motor Adaptation (AMA)
and press [OK].
5.
Select [1] Enable complete AMA and press [OK].
6.
Follow on-screen instructions.
7.
The test runs automatically and indicate when it
is complete.

5.5 Checking Motor Rotation

NOTICE
Risk of damage to pumps/compressors caused by motor
running in wrong direction. Before running the
frequency converter, check the motor rotation.
The motor runs briefly at 5 Hz or the minimum frequency
set in 4-12 Motor Speed Low Limit [Hz].
1.
Press [Main Menu].
2.
Scroll to 1-28 Motor Rotation Check and press
[OK].
3.
Scroll to [1] Enable.
The following text appears: Note! Motor may run in wrong
direction.
4.
Press [OK].
5.
Follow the on-screen instructions.
NOTICE
To change the direction of rotation, remove power to
the frequency converter and wait for power to discharge.
Reverse the connection of any 2 of the 3 motor wires on
the motor or frequency converter side of the connection.
MG21B202