Weight Density Over; Feed Rate Over; Load Ratio Over - Unipulse F805AT-BC Operation Manual

Belt scale controller
Table of Contents

Advertisement

6-4-7. Weight density over

Over scale alarm "OFL2" is activated when weight density becomes greater than
WEIGHT DENSITY OVER set value. Comparison is disabled if the value is set to
99999. Also, the comparison is disabled if [WEIGHT DENSITY OVER OVER ASC.]
is set to zero second.
Operation
MODE
Range: 0 – 99999 kg/m (5 digits, decimal place floating)

6-4-8. Feed rate over

Over scale alarm "OFL3" is activated when the feed rate becomes greater than FEED
RATE OVER set value. The unit for this value is either kg/h or t/h depending on the
selection in [FEED UNIT]. Comparison is disabled if the value is set to 99999. Also,
the comparison is disabled if [FEED RATE OVER ASC.] is set to zero second.
Operation
MODE
Range: 0 – 99999 (5 digits, decimal place floating)

6-4-9. Load ratio over

Over scale alarm "OFL4" is activated when the load ratio becomes greater than LOAD
RATIO OVER set value. Comparison is disabled if the value is set to 999.99. Also, the
comparison is disabled if [LOAD RATIO OVER ASC.] is set to zero second.
Operation
MODE
Range: 0 – 999.99 % (5 digits, decimal place fixed)
COMPARISON
→ WEIGHT DENSITY OVER
COMPARISON
PAGE
COMPARISON
PAGE
6.SETTING AND ADJUSTMENT OF READING
→ FEED RATE OVER
→ LOAD RATIO OVER
63