6.SETTING AND ADJUSTMENT OF READING
6-1-7. Dead band load ratio
While the value of DEAD BAND LOAD RATIO (%) is greater than LOAD RATIO
(%), F805AT-BC turns on "NZ" status indicator and set the NZ external signal to
"ON". Accumulation is not performed in this state. Setting DEAD BAND LOAD
RATIO to zero disables accumulation calculation.
Operation
MODE
Input Range: 0 – 99 % (2 digits)
6-1-8. Dead band belt speed
F805AT-BC performs arithmetic calculations assuming the belt speed to be 0.00 m/min
if:
Belt speed [m/min] < Rated belt speed [m/min] × Dead band [%]/100
Operation
MODE
Input Range: 0 – 99 % (2 digits)
6-1-9. Moisture ratio
This parameter specifies the moisture content (%) of the material to be conveyed.
Moisture is excluded from accumulation calculation. This value does not affect weight
density, feed rate, load rate, and feed ratio measurements.
Operation
MODE
Input Range: 0 – 99 % (2 digits)
48
OPERATION
DEAD BAND LOAD RATIO
→
→
OPERATION
DEAD BAND BELT SPEED
→
→
OPERATION
PAGE
→
→
→ MOISTURE RATIO