Item
Operation method
Fan speed of
Select [High] or
interlocked
[Low].
LOSSNAY
Select [Available] or
Schedule
[Not Available].
Select [ON] or
Hold
[OFF].
Filter Sign
Select [Reset] and
Reset
click [Send].
Click the operation
Prohibit
item to switch the
Remote
setting between
Controller
"Prohibit" and
Operation
"Permit".
Send
Click [Send].
Close
Click [Close].
* After [Send] is clicked, it takes a while for the status of the LOSSNAY unit group icons to be updated.
* If a LOSSNAY unit is interlocked with the operation of indoor units in multiple groups, the LOSSNAY unit may be in operation, even when
the LOSSNAY unit is displayed as "stopped".
WT07996X02
Switches the fan speed of the interlocked LOSSNAY units (ventilator).
Enables/Disables the schedules.
Note: When [Not Available] is set, the scheduled operations are disabled even if
schedules are set.
Note: The operations that have been scheduled on the remote controller will not
be disabled.
Enables/Disables the Hold function. When the Hold function is enabled, the
scheduled operations are disabled.
Note: The operations that have been scheduled on the remote controller will also be
disabled.
Note: [Hold type] can be specified in the [Advanced] screen in the initial settings.
Refer to the Instruction Book (Initial Settings) for details.
Note: The Hold function can be used on the AE-200A/AE-50A/EW-50A, but not on the
AE-200E/AE-50E/EW-50E.
Resets the filter sign. (The cumulative time will be reset.)
When resetting, ensure the check mark is displayed as "
Note: Reset the filter sign after cleaning the filter.
Note: After the filter sign is reset, it takes up to an hour to clear the filter sign display
on the local remote controllers.
The following operations or setting change can be prohibited from the local remote
controllers and when the Integrated Centralized Control Web is logged in with
general user privileges: ON/OFF, Operation mode, Set temperature, Filter Sign
Reset, Air Direction, Fan Speed, and Timer.
: Permit
: Prohibit
Note: If "Timer" operation is prohibited, scheduled operations set on the local remote
controller will be disabled.
Click to reflect the changes made and return to the group list.
Click to return to the group list without making any changes.