Factory Configuration - Wilo Geniax Central Control User Manual

Table of Contents

Advertisement

Technical information
13.2 Technical data
Electronics
Electromagnetic compatibility
Emitted interference
Interference resistance
Protection class
Protection class
Materials
Housing
1) In the range of +15 to +25°C
2) Device active, display lighting switched on
3) can be activated/deactivated via the termination switch (DIP switch) at the Central Control

13.3 Factory configuration

Temperature pre-settings
Comfort temperature
Energy saving temperature
Minimum temperature
Maximum temperature
Room frost protection tempera-
ture
Temperature in the day period
End of the day period
Temperature in the night period
End of the night period
User manual Wilo-Geniax Central Control
EN 55022
EN 61000-6-3
EN 61000-6-2
IP 20
II
Lower part of housing: Plastic PC-ABS
Housing, upper part: Plastic PMMA/PC
The normally used factory-saved values are presented in
the following table.
21°C
The default value of the Geniax System which
is suggested when creating a new time area
in the week profile.
16°C
The default value of the Geniax System for
absence.
10°C
The lowest room temperature which can be
set for the building/rooms.
30°C
The highest room temperature which can be
set for the building/rooms.
8°C
The frost protection temperature set for all
rooms in the building by the Geniax System.
The value of the frost protection temperature
can be below the minimum temperature.
21°C
The temperature set by the Geniax System
for presence.
22:00 hrs The end of the day period set by the Geniax
System.
16°C
The temperature set by the Geniax System
for absence.
06:00 hrs The end of the night period set by the Geniax
System.