Three-Phase Adjustment - Aquacal Water Source WS03 Installation Manual

Hide thumbs Also See for Water Source WS03:
Table of Contents

Advertisement

2.11 Three-Phase Adjustment

DANGER
Deactivate power while routing wiring to control board.
l
Follow all National Electric Codes (NEC) and/or State and Local guidelines.
l
WARNING
The information contained in this section is intended for use by qualified technicians, familiar with electrical
l
service-industry safety standards and methods.
NOTICE
Setting a voltage other than what is listed on the heat pump's data plate can damage equipment and is not
l
covered under warranty.
If a three-phase unit fails to operate at start-up, the orientation of the line voltage "field" wiring may need
to be adjusted.
Three-phase models are equipped with a Three-Phase Monitor or the ICM Digital Three-Phase Monitor.
l
Units equipped with the ICM Digital Three-Phase Monitor will display a "Back Phase Rev" fault code on the
l
phase monitor display.
There is no display on the standard three-phase monitor.
l
The phase monitor is located inside the electrical panel.
l
PLEASE NOTE
The WS10 Water Source heat pump comes with an ICM
phase-rotation monitor. All other three-phase models use
the standard phase-rotation monitor. These monitors are
located inside the electrical panel.
The device protects the heat pump by preventing
operation during abnormal voltage conditions.
If the unit fails to operate, a qualified technician
l
should check the phase rotation monitor for faults
preventing operation. Complete instructions for the
ICM phase monitor are in the appendix. See "ICM Digital 3-Phase Monitor" on
page 71.
Failure to heed the following will result in injury or death.
Failure to heed the following may result in injury or death.
Failure to heed the following may result in damage to equipment.
Standard
ICM Digital
Three-Phase
Three-Phase
Monitor
Monitor
Page - 77

Advertisement

Table of Contents
loading

This manual is also suitable for:

Water source ws05Water source ws10Sunpower sp05