Aquacal Water Source WS03 Installation Manual page 26

Hide thumbs Also See for Water Source WS03:
Table of Contents

Advertisement

USE ARROWS TO
1
"EXTERNAL CONTROL"
ENTER TO EDIT
4
USE ARROWS TO SET
7
LOCAL ADDRESS
PLEASE NOTE:
This action will wipe all previous settings
in favor of the new configuration. This
includes external controller settings,
optional device settings, groups,
equipment, schedules, and site specific
settings. Additional site specific settings
may need to be put in place.
10. If after 45 seconds, the heat pump displays a
A. Confirm dip switches - If external controller uses dip switches, confirm switches are in the correct
position. Otherwise, proceed to confirm wiring.
a. Deactivate power to the external controller.
b. Remove access panel on external controller.
c. Check the external controller manual for proper dip switch positioning and confirm dip switches.
d. Reinstall electrical access panel.
e. Reactivate power to the controller.
f. If the fault persists, proceed to confirm wiring.
B. Confirm wiring - Confirm wires are oriented properly on the heat pump's "Port B" of the control board.
a. Deactivate power to heat pump and external controller.
b. Remove the access panel on the heat pump.
c. Reverse wires on "Port B".
d. Reinstall electrical access panel.
7. Reactivate power to the controller.
8. Reactivate power to the heat pump.
C. If fault continues to occur, check with the manufacturer of the external controller for additional advice on
using a heat pump with the controller.
Page - 22
ENTER TO SELECT
2
ARROWS TO
5
"SMART"
ENTER TO SAVE
8
The system will restart. If successful, the
heat pump should now display "Under
Remote Control".
"SMART COMM
ARROWS TO MODE
3
ENTER TO SAVE
6
CONFIRM OK TO CLEAR
9
ANY EXISTING SETUPS
FAULT":