7.5.4 Wiring 5815XL or 6815 in Class A Configuration
Figure 7.3 illustrates how to wire the SLC loop for Class A installations.
NOTE: Class A wiring also requires an isolator module as the first device on the in and the out loops.
NOTE: No t-taps allowed on class A SLC loops.

7.6 Wiring SK SLC Detectors

This section describes how to install SK heat and smoke detectors. See Table 7.1 for a list of detectors. Refer to the detectors' installation
instructions for more detailed information.
To wire SK detectors:
1.
Wire device bases as shown in Figure 7.4.
2.
Set the address for each device as described in Section Figure 7.7

7.7 Addressing SK SLC Devices

All SK devices are addressed using the two rotary dials that appear on the device board. Use the ONES rotary dial to set the ones place in
a one or two digit number, and use the TENS rotary dial to set the tens place in a two or three digit number.
92
Figure 7.3 Class A SLC Configuration
Figure 7.4 Heat and Smoke Detector Connection to the Panel.