Auxiliary Circuit Current Consumption; Definitions; Inverter Units For Increased Switching Frequency - ABB ACS880 Manual

Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

Auxiliary circuit current consumption

Component
Cooling fan (+C188)
Cooling fan (+C188+G427)
Heating element (option +C183)

Definitions

U
Voltage requirement
N
f
Supply frequency
I
Continuous current consumption
cont
I
Calculated load current at start
start
P
Continuous input power
cont

Inverter units for increased switching frequency

The table below shows the inverter units for increased switching frequency (ie. with option
+P967), available as modules or as cabinet-built. Note that +P967 is not always needed in
high-speed applications – see
Options +C183 (heating element) and +G304 (single-phase 115 V AC fan supply voltage)
are available for all listed types.
Inverter unit type
as modules
cabinet-built
ACS880-
ACS880-
104-...
107-...
U
= 400 V
N
1250A-3+E205+P967
1860A-3+E205+P967
2450A-3+E205+P967
3050A-3+E205+P967
3640A-3+E205+P967
4250A-3+E205+P967
4860A-3+E205+P967
U
= 500 V
N
1150A-5+E205+P967
1710A-5+E205+P967
2260A-5+E205+P967
U
N
V
400 V AC ±10%
400 V AC ±10%
320 V AC ±10%
208 V AC ±10%
115 V AC
230 V AC
Description of the high-speed option (page
Input ratings
Frame size
I
1
A
2×R8i
1406
3×R8i
2093
4×R8i
2756
5×R8i
3431
6×R8i
4095
7×R8i
4826
8×R8i
5468
2×R8i
1294
3×R8i
1924
4×R8i
2543
f
I
cont
Hz
A
50
1.50
60
1.90
60
-
60
2.88
60
-
50/60
-
Output ratings
No-overload
Light-over-
use
load use
I
I
2
Ld
A
A
1250
1200
1860
1786
2450
2352
3050
2928
3640
3494
4250
4080
4860
4666
1150
1104
1710
1642
2260
2170
Technical data 51
I
P
start
cont
A
W
3.00
-
3.80
-
4.40
-
-
-
-
13
-
13
13).
Heavy-duty
use
I
Hd
A
935
1391
1833
2281
2723
3179
3635
860
1279
1690

Advertisement

Table of Contents
loading