Definitions; Switching Frequency And Output Frequency Derating; Ambient Temperature And Altitude Derating - ABB ACS880 Manual

Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

52 Technical data
Inverter unit type
as modules
cabinet-built
ACS880-
ACS880-
104-...
107-...
2810A-5+E205+P967
3360A-5+E205+P967
3920A-5+E205+P967
4480A-5+E205+P967
U
= 690 V
N
1170A-7+E205+P967
1740A-7+E205+P967
2300A-7+E205+P967
2860A-7+E205+P967
3420A-7+E205+P967
3990A-7+E205+P967
4560A-7+E205+P967
5130A-7+E205+P967
5700A-7+E205+P967

Definitions

U
Nominal AC supply voltage of drive system
N
I
Nominal rms input current
1
I
Nominal output current (available continuously with no over-loading)
2
I
Continuous rms output current allowing 10% overload for 1 minute every 5 minutes
Ld
I
Continuous rms output current allowing 50% overload for 1 minute every 5 minutes
Hd

Switching frequency and output frequency derating

Contact your local ABB representative for information.

Ambient temperature and altitude derating

See ACS880-107 inverter units hardware manual (3AUA0000102519 [English]) or
ACS880-104 inverter modules hardware manual (3AUA0000104271 [English]).
Input ratings
Frame size
I
1
A
5×R8i
3161
6×R8i
3780
7×R8i
4410
8×R8i
5040
2×R8i
1316
3×R8i
1958
4×R8i
2588
5×R8i
3218
6×R8i
3848
7×R8i
4489
8×R8i
5130
9×R8i
5771
10×R8i
6413
Output ratings
No-overload
Light-over-
use
load use
I
I
2
Ld
A
A
2810
2698
3360
3226
3920
3763
4480
4301
1170
1123
1740
1670
2300
2208
2860
2746
3420
3283
3990
3830
4560
4378
5130
4925
5700
5472
Heavy-duty
use
I
Hd
A
2102
2513
2932
3351
875
1302
1720
2139
2558
2985
3411
3837
4264

Advertisement