Mitsubishi Electric NZ2GF-ETB User Manual page 196

Cc-link ie field network ethernet adapter module
Table of Contents

Advertisement

(1) Restrictions of the IP address setting range
Restrictions apply to IP addresses that can be set to perform the communications described on the next page.
Build the system so that the IP address within each setting range described on the next page can be set.
• When accessing to the master station with SLMP
Decimal notation
192. 168. 3. 30
• When connecting to MELSOFT from GX Works2
Decimal notation
192. 168. 3. 30
• When connecting to MELSOFT from a GOT
Decimal notation
192. 168. 3. 30
• When communicating with an external device over CC-Link IE Field Network (IP packet transfer function)
Decimal notation
192. 168. 3. 30
● For the third octet of the IP address, do not set the same value as the network number of CC-Link IE Field Network.
● To perform IP communications over CC-Link IE Field Network (IP packet transfer function), set the same first and second
octets of the IP address as those of the master station and submaster station. When these numbers are different,
configure the CC-Link IE Field Network gateway setting. ( Page 107, Section 7.3, Page 191, Section 10.3.2 (1))
194
1 to 120
1 to 239
1 to 255
1 to 239
1 to 64
1 to 239
1 to 120
1 to 239
Hexadecimal notation
C0. A8. 03. 1E
Hexadecimal notation
C0. A8. 03. 1E
Hexadecimal notation
C0. A8. 03. 1E
Hexadecimal notation
C0. A8. 03. 1E
1 to 78
1 to EF
1 to FF
1 to EF
1 to 40
1 to EF
1 to 78
1 to EF