Mitsubishi Electric NZ2GF-ETB User Manual page 222

Cc-link ie field network ethernet adapter module
Table of Contents

Advertisement

Number
Name
Connection status (own
SW0064
station)
220
The connection status of the own station is stored.
00
: Normal
H
01
: Normal (communicating on PORT1, cable disconnected on PORT2)
H
04
: Normal (loopback communicating on PORT1, cable disconnected on PORT2)
H
10
: Normal (cable disconnected on PORT1, communicating on PORT2)
H
11
: Disconnected (cables disconnected on PORT1 and PORT2)
H
12
: Disconnected (cable disconnected on PORT1, PORT2 line being established)
H
21
: Disconnected (PORT1 line being established, cable disconnected on PORT2)
H
22
: Disconnected (PORT1 and PORT2 lines being established)
H
40
: Normal (cable disconnected on PORT1, loopback communicating on PORT2)
H
Description