Mitsubishi Electric NZ2GF-ETB User Manual page 167

Cc-link ie field network ethernet adapter module
Table of Contents

Advertisement

End code or
error code
0310
Data length error
H
0311
Request message error
H
0312
Target station No. error
H
0313
Target station No. error
H
0314
System error
H
0315
IP communication test in progress
H
0316
IP communication test execution error (no response to Ping)
H
0380
Request source ID error
H
0381
Receive error
H
0382
Receive queue full
H
0383
Send error
H
0384
System error
H
0400
ASCII conversion error
H
0401
Word device read/write size error
H
0402
Bit device read/write size error
H
0403
Random read/write bit device size error
H
0404
Random read/write word device size error
H
0405
File size error
H
0406
Address range error
H
0407
Unsupported command
H
0408
Device name error
H
0409
Unsupported device specified
H
040A
Device access type error
H
040B
Unregistered monitoring
H
040C
Response monitoring timer timeout
H
040D
ACK error
H
040E
Request data error
H
Error and cause
CHAPTER 9 TROUBLESHOOTING
Action
• Correct the read or write data length.
• When the read or write data length is too long, divide it into parts for a
command request.
Retry the transient transmission.
Correct the request command at the transient request source, and retry the
operation.
Please consult your local Mitsubishi representative.
Retry the IP communication test after a while. (Up to four IP communication
tests can be concurrently executed.)
• Check "Communication Target" in the "IP Communication Test" dialog
box.
• Check and correct the status of the cable connection and line between
the CC-Link IE Field Network gateway setting station and the
communication destination.
• Enable a response to the Ping command (ICMP echo request) in the
firewall settings on the external device or antivirus software.
Restart the Ethernet adapter module. If the same error is displayed again,
please consult your local Mitsubishi representative.
When the receiving station encountered overloading of transient data, send
the data from the source after a given time has elapsed.
Reduce the frequency of transient transmission and then retry the
operation.
Please consult your local Mitsubishi representative.
• Set "Binary Code" in the configuration tool, and restart the Ethernet
adapter module to start communication.
• Correct the data sent from the external device.
• Correct the setting for the subcommand.
• Check the device settings.
Correct the number of read or write points, and send the data to the
Ethernet adapter module again.
Correct the number of read or write points (or bytes), and send the data to
the Ethernet adapter module again.
Correct the start address or the number of read or write points, and send the
data to the Ethernet adapter module. (Do not exceed the maximum address
number.)
Check and correct the request data.
Correct the device, and read or write the device again.
Correct the request data (e.g. the subcommand), and send them to the
Ethernet adapter module again.
Register the monitoring data before start monitoring.
• Increase the monitoring timer value.
• Check if the Ethernet adapter module is operating properly.
• Correct the network or station number.
• If a station with another network number is set as the destination, correct
the routing parameter value.
• If a station with another network number is set as the destination, check
the network number for duplication.
• Confirm the IP address. ( Page 193, Section 10.3.3)
• Correct the network or station number.
• Correct the I/O number of the target module.
• Correct the read or write request data.
Correct the request data, and send them to the Ethernet adapter module
again.