● Set the IP address of CC-Link IE Field Network in the master station and submaster station. When the IP address is set,
the IP address is automatically assigned to the CC-Link IE Field Network part on the Ethernet adapter module. The IP
address to be assigned is as follows.
IP address
● The assigned IP address can be checked using the Ethernet adapter diagnostics of the configuration tool in the Ethernet
adapter module.
[Online]  [Diagnostics]  [Module Information] button
The IP address can be also checked using the CC-Link IE Field Network diagnostics of GX Works2. ( User's manual for
the master/local module used)
● If the IP address is not displayed, check that the D LINK LED is on, and check Baton pass status (own station) (SW0047)
to see whether baton pass can be performed.
114
.
. 1 . 1
Station No. of the Ethernet adapter module
Network No. of the Ethernet adapter module
The 1st and 2nd octets of the IP address set