WARNING: The router is a pluggable type
location. It has a separate protective earthing terminal provided on the chassis and on
the DC power supply module in addition to the grounding pin of the AC power supply
cord. You must keep this separate protective earthing terminal permanently connected
to earth ground for installations that require a separate grounding conductor to the
chassis.
WARNING: To comply with GR-1089 requirements, all intra-building copper cabling
used for SFP+ and QSFP+ ports must be shielded and grounded at both ends.
CAUTION: Before you install the router, a licensed electrician must attach a cable lug to
the grounding cables that you supply. See
Routers" on page
Before you connect the router to earth ground, review the following information:
• The grounding points are in the form of studs that are sized for #10-32 screws. You need to provide
these screws with integrated washers as we do not ship them in the accessory kit.
• For ACX7100-32C routers, the grounding lug required is a Panduit LCD10-10A-L or equivalent. The
grounding lug accommodates 14–10 AWG (2–5.3mm²), stranded wire.
66. A cable with an incorrectly attached lug can damage the router.
A equipment installed in a restricted-access
"Connect Earth Ground to ACX7100-32C
37