Eaton 93PS UPS 8–40 kW
Load power factor (rated)
Load power factor (permitted range)
Max ambient temperature without de-rating 40 °C
9.4
Acoustic noise at 1 m
Ambient storage temperature
Transportation temperature
Ambient operating temperature range
Relative humidity range
Maximum service altitude
Maximum storage time with internal batter-
ies
* Maximum recommended operating and storage temperature for UPS with internal bat-
teries is +25 °C. Higher storage temperature will shorten the maximum storage time
without recharging.
1)
The maximum recommended operational and storage temperature with VRLA batter-
ies is 25 °C.
9.5
Battery type
Battery quantity
Battery voltage
Recharge profile
©
Eaton Corporation plc 2016. All rights reserved.

UPS environmental specifications

1)

Battery specification

Nominal 1.0
From 0.8 lagging to 0.8 leading
40 kW unit: <55 dB at 75% load
40 kW unit: <60 dB at 100% load
From -25 °C to +55 °C in the protective
package
From -25 °C to 60 °C
From 0 °C to +40 °C*
5 to 95%, no condensation allowed
1,000 m (3,300 ft) above sea level at +40
°C
Maximum 2,000 m (6,600 ft) with 1% de-
rating per each additional 100 m above
1,000 m.
6 months without recharge
VRLA, 12 VDC
Default 32 blocks, 192 cells per battery
string
External battery 28–40 blocks, 168–240
cells per battery string
Note! Do not connect battery strings with
different battery quantity and voltage in
parallel!
384 V (32 blocks), 336 V (28 blocks), 480
V (40 blocks)
Constant voltage, constant current charg-
ing (U-I characteristics), ABM or float
charge
Revision: 003
Document ID: P-164000493
User's and installation guide