4.8.3
Flux Loop
Regulation of motor flux is accomplished with the flux control loop. The output of the flux loop
forms the magnetizing current command (I
induction motor applications. For synchronous motor applications, use lower gains. Flux loop
gains require tuning when the regulator output shows significant oscillations during steady
state operation.
NXGPro+ Control Manual
Operating Manual, A5E50491925A
NXGPro+ Control Description
4.8 Advanced Functions Control Loops
). The default flux loop gains work well for most
ds,ref
61