Parameter Assignment/Addressing
6.6 Options for Drive Menu (2) - second part
Table 6-44
Internal Analog Output 8 Menu (2685) Parameters
Parameter
ID
Analog variable
2686
Output Mode
2688
Output Min
2681
Output Max
2682
Hardware Zero
2683
Hardware Span
2684
Output Default
2687
Table 6-45
Pick list for Internal Analog Output Source
Motor Voltage
Total Current
Average Power
Motor Speed
Speed Demand
Speed Reference
Raw Flux Demand
Flux Reference
Current (RMS)
Zero Sequence Av
Neg Sequence D
Table 6-46
Output Connection Menu (2900) Parameters
Parameter
ID
Filter CT sec
2910
turns
Filter Currents
2918
Source
Filter induc‐
2920
tance
122
Unit
Default
Min
1
0
%
0
-300
%
100
-300
0
-200
1
0.75
%
0
0
Neg Sequence Q
Input Frequency
Input Power Avg
Input Pwr Factor
Ah Harmonic
Bh Harmonic
Total Harmonics
Xfmr Therm Level
1 Cycle Protect
Single Phase Cur
Under Volt Limit
Unit
Default
0
Filter CTs
%
0.0
Max
Description
Internal analog output 8 source pick list.
See Pick list for Internal Analog Output Source.
Internal analog output 8 mode:
4 to 20 mA
0 to 20 mA
300
Internal analog output 8 minimum
300
Internal analog output 8 maximum
200
Internal analog input 8 zero
1.25
Internal Analog Input 8 span
100
Analog output 8 watchdog default value
Out Neutral Volts
Synch Motor Field
Motor Torque
Encoder Speed
Analog Input #1
Analog Input #2
Analog Input #3
Analog Input #4
Analog Input #5
Analog Input #6
Analog Input #7
Min
Max
0
250
0.0
20.0
Analog Input #8
Input KVAR
Drive Losses
Excess React Current
Speed Droop Percent
Torq Current (Iqs) Ref
Torq Current (Iqs) Fb
Torq Current (IqsFilt) Filtered
Description
Assuming primary turns = 5, sec‐
ondary side turns of the CTs is used
to measure filter capacitor cur‐
rents (not used if Filter Currents
Source is set to "output CTs")..
Sets the source of filter current val‐
ues used in the compensation al‐
gorithm.
Set the output filter inductor, i.e.
impedance value, as a ratio of the
base output impedance of the
drive; typically 5%.*
NXGPro+ Control Manual